Characterization and Error Compensation of a Rogowski Coil in the Presence of Harmonics

2011

This paper reports the results of an experimental study dealing with a commercial Rogowski coil current transducer (RCCT) in the presence of harmonic distortion. The RCCT was observed under two conditions: 1) sinusoidal excitation with frequencies from 50 to 750 Hz and 2) nonsinusoidal excitation using fundamental frequency and one harmonic, with adjustable amplitude and phase shift. The experimental results show only a weak dependence of the harmonic current ratio error and phase displacement on the amplitude and phase shift of the excitation harmonic. The phase displacement is also independent of the conductor position within the Rogowski coil window. An error compensation method, based o…

PhysicsTotal harmonic distortionFrequency responsebusiness.industryAcousticsElectrical engineeringFundamental frequencycurrent transducerRogowski coilCurrent measurement current transducer frequency response harmonic distortion power system harmonics Rogowski coil.harmonic distortionHarmonic analysisAmplitudeHarmonicsHarmonicpower system harmonicElectrical and Electronic EngineeringbusinessInstrumentationSettore ING-INF/07 - Misure Elettriche E ElettronicheRogowski coil
researchProduct

Improvement of Hall Effect Current Transducer Metrological Performances in the Presence of Harmonic Distortion

2010

The performance of Hall effect current transducers (HECTs), under distorted waveform conditions, is usually characterized by means of a frequency response test. In this paper, it was investigated if frequency response is able to correctly evaluate the ratio and the phase errors under distorted conditions. Two HECTs, with the accuracy class level of 1% and 0.5%, respectively, were experimentally characterized under two conditions: 1) sinusoidal excitation with frequencies ranging from 50 to 750 Hz, which is the well-known frequency response test, and 2) nonsinusoidal excitation using fundamental frequency and one harmonic with adjusted amplitude and phase shift. It was found that ratio and p…

Frequency responseElectric current measurementCurrent measurement current transducer frequency response hall effect devices harmonic distortion power system harmonics.AcousticsTransducersPhase (waves)GyratorsNon-sinusoidal excitationHarmonic distortionAccuracy levelFundamental frequenciesHarmonic analysisPhase errorElectric currentsError compensationFrequency responseFrequency response testsWaveformSinusoidal excitationsPhase shiftElectrical and Electronic EngineeringInstrumentationPhysicsTotal harmonic distortionElectric power distributionHall effectCurrent measurementsMetrological performanceCurrent transducerFundamental frequencyLight measurementAmplitudeAccuracy classHarmonicsMagnetic field effectsHarmonicHarmonic amplitudeSettore ING-INF/07 - Misure Elettriche E ElettronicheDistorted waveformsHarmonic componentsHall effect devicesIEEE Transactions on Instrumentation and Measurement